NST4/4.0

4 x 4.0mm²


Standard Performance Fixed Neutral Screen Cable 0.6/1kV 90°C


Keywords: NST Trayscreen, motor cabling, lighting circuits, cable tray

 

Click to download full series data sheet

Click to download Compliance Document

Quantity of item required. Cable is quoted in metres.

APPLICATIONS:


Trayscreen Commercial cable tray installations.

Consumer Mains Domestic and commercial - only suitable for burial with added protection or in conduit.

Internal Wiring Fixed applications between distributions boards.

Motor Cabling Fixed applications between motor control and electric motors.

Lighting Circuits Fixed applications for lighting circuits where mechanical protection is required.



PRODUCT FEATURES:



  • 1.8mm SPVC Sheath, Smaller OD compared to standard NS Cables

  • PVC sheath for ease of installation

  • Metre marked for better length control

  • UV Stabilised

  • Flame retardant

  • Heat, oil and chemical resistant


CONSTRUCTION:


Conductor Annealed plain copper stranded (Class 2).

Insulation V-90.

Sheath SPVC.


CHARACTERISTICS:


Operating Temperature Range -15 to 90°C

Maximum Conductor Temperature 90°C (Current ratings are based on 30°C air temp. See technical section for de-rating factors).

Rated Voltage Uo/U 0.6/1kV.

Minimum Bending Radius Fixed 12 x cable diameter.

Sheath Colour Black.

Standard Core Colours

2 Cores: Red, White.

3 Cores: Red, White, Blue.

4 Cores: Red, White, Blue, Black.

Relevant Standards AS/NZS 1125, AS/NZS 3808, AS/NZS 4961, AS/NZS 5000, ROHS Compliant.


CERTIFICATE OF COMPLIANCE: Neutral Screen SDoC

No. of Cores x Size (mm²): 4 x 4.0

Approx. Stranding Power (No. of wires x mm): 7/0.85

Approx. Overall Diameter (mm): 16.8

Nominal Outer Sheath Thickness (mm): 1.8

Approx. Weight (Kg/Km): 490

Nominal Amps @ 30°C Fixed Installation
Wiring enclosure in air (touching):
33
Enclosed wiring enclosure in air:
29
Under ground wiring:
36

Three Phase Volt Drop @ 75°C (Mv/Am): 9.71