HFX185

1 x 185.0mm²


Ultra Performance Flexible Rubber LSHF SDI Cable 0.6/1kV 110°C


Keywords: HFX Series, LSZH, Low Smoke Halogen Free, Greenstar, Single Double Insulated, Power, Data centres, Welding, Telecommunications

 

Click to download full series data sheet

Click to download Compliance Document

Quantity of item required. Cable is quoted in metres.

APPLICATIONS:


Data Centers: LSHF cables boost safety, minimize toxic emissions, ensure compliance, and provide reliable performance in high-density cabling applications.

Power Supply: for Switchboards, flexible droppers from busbars, transformers, load banks or other equipment requiring fixed or flexible cable.

Welding: Suitable for welding and electrode leads.

Generator Sets: As leads for temporary power supplies.

Automotive: Battery leads or jumpers, battery chargers, electric forklifts.

Telecommunications: Where finely stranded large cross section cables are required for minimal volt drop.

Greenstar applications: PVC-free, Low Smoke Halogen Free construction suitable for sustainable building standards.



CONSTRUCTION:


Conductor: Annealed plain copper stranded extreme flexibility (Class 6)

Insulation: X-HF-110

Sheath: SE-LSHF-EG


CHARACTERISTICS:


Operating Temperature Range: Fixed -25°C to 110°C

Maximum Conductor Temperature: 110°C (Current ratings are based on 30°C air temp. See technical section for de-rating factors).

Rated Voltage: Uo/U 0.6/1kV.

Max AC Operating Voltage: Uo 0.7kV.

Minimum bending radius after installation: Fixed 4 x cable diameter / Flexing 6 x cable diameter.

Sheath Colour: Black (other colours available on request)

Relevant Standards IEC 60332-1, AS/NZS 5000.1, AS/NZS 1125, AS/NZS 3808, AS/NZS 3008, IEC 61034-2, IEC 60754-1, ROHS Compliant.


COMPLIANCE DOCUMENT:


HFX Series SDoC

Product Code: HFX185 Categories: ,

Size: 1 x 185.0mm²

Approx stranding no. of wires x mm: 2660/0.284

Approx overall diameter (mm): 24.6

Approx weight (Kg/Km): 1820

Nominal Amps un-enclosed @30°C fixed installation 3 Phase - Spaced: 689

Nominal Amps un-enclosed @30°C fixed installation 3 Phase - Spaced from surface: 592

Nominal Amps un-enclosed @30°C fixed installation 3 Phase - Touching: 552

3 Phase Volt Drop @50Hz / MAX. Conductor Temp: 110°C (Mv/Am): 0.296