APPLICATIONS:
Power Suitable for mains and submains in a fixed application.
 Direct Burial Can be installed underground when installed as part of a Category B wiring system.
 Outdoor Use Suitable for outdoor use and wet locations not subject to mechanical damage.
 Flexible Class 5 conductors for easy installation in fixed applications.
 Hazardous Areas With correct explosion proof glands this cable can be installed in locations subject to explosion hazards AS/NZS 60079.14.
PRODUCT FEATURES:
- Flexible Class 5 conductors for easy installation
- Suitable for circuits buried direct
- Metre marking for better length control
- UV stabilised
- Flame retardant
- Heat, oil and chemical resistant (see Chemical Rating Chart)
CONSTRUCTION:
Conductor Annealed plain copper stranded high flexibility (Class 5).
 Insulation X-90.
 Sheath SPVC.
CHARACTERISTICS:
Operating Temperature Range Fixed -20°C to 90°C.
 Maximum Conductor Temperature 90°C. (Current ratings are based on 30°C air temp. See technical section for de-rating factors).
 Rated Voltage Uo/U 0.6/1kV.
 Minimum Bending Radius Fixed 12 x cable diameter.
 Sheath Colour Black.
 Standard Core Colour
 3 core – Red, Black, Green/Yellow.
 4 core – Red, White, Blue, Green/Yellow.
 5 core – Red, White, Blue, Black, Green/Yellow.
 Relevant Standards AS/NZS 5000.1, AS/NZS 1125, AS/NZS 3008, AS/NZS 3808, IEC 60332-1-2, AS/NZ 60079.14 ROHS Compliant. BEP Certified – Greenstar compliant.