- Marine LSHF Flexible Tinned Copper and Lloyds Approved cable for installation in Oil and Gas Rigs, Shipboard and other marine applications.
- Pumping Suitable for permanent submersion to 500 metres
- Greenstar Applications With its PVC free materials and Low Smoke Halogen Free features this cable is suitable for greenstar installations.
- Transport Suitable for wiring in trains and buses
|
 |
- Conductor Annealed fine wires of tinned electrolytic copper stranded for HIGH flexibility BS6360 Class 5
- Insulation EPR Type GP4 R90 (BS6899, BS6883 1991)
- Sheath EVA Compound (Type D BS6883 1991). Oxygen index greater than 32%
|
 |
- Temperature Range Fixed -40 to 90°C / Flexing -20 to 90°C
- Rated Voltage Uo/U 0.6/1Kv Max AC Operating Voltage Uo 0.7Kv
- Minimum Bending Radius Fixed 7.5 x cable diameter / Flexing 10 x cable diameter
- Sheath Colour Black.
- Standard Core Colour
2 Core - Blue, Brown
3 Core - Blue, Brown, G/Y
4 core - Brown, Black, GREY, Green/Yellow
5 Core - White Numbered, G/Y
Multicore - White Numbered, G/Y
- Maximum Conductor Temperature 90°C
- Certification Society Approvals A.B.S., LLOYDS, B.V., DNV, RINA
- Relevant Standards BS6899, BS6883, BS7655, BS6360, AS/NZS4193, IEC754-1, IEC754.2, IEC1034, IEC60332-1+3, IEC92350, Generally
to AS/NZS 5000:2003, CE Directive 72/23/EEC
|
 |
- Tinned fine stranded copper conductor
- Low Smoke Halogen Free
- PVC Free
- UV Stabilised
- Flame retardant
- Heat, oil and chemical resistant (refer to chemical chart)
- Water and moisture resistant
- Resistant to environmental factors like oxidation, ozone and sunlight
- Very good behaviour to variations of outdoor temperature
- Good tensile strength, tearing strength and abrasion resistance
- Good elongation at break
- Good dielectric properties for permanent submersion to 500 metres
|
|
|
|
|
|